Precaution before operation of Handsome II air compressor
Precaution before operation of Handsome II air compressor
1.1 Unloading
Refilling oil
Unit: L
Caution: The pressure remains in the oil separator for one minute after shutdown. Fill oil under no pressure.
Draining oil
If the transformer is too small or the wiring is too thin and too long, the motor may not accelerate sufficiently or may fail to start because of a sharp voltage drop at the start. Select a transformer of an adequate capacity for the motor considering proper wiring size and routing.
Selection of power supply breaker:
When installing the breaker for the main power supply, select an earth leakage circuit breaker.
600V rated CV cables:
( JIS C306-93)
Remove the front cover of the enclosure and the power unit box cover, and connect the cables to the power supply terminals.
Earth wire:
Note: When using a cable with a sectional size more than 60mm2, use a relay terminal so that the cable size on the local side will be 60mm2, or select a crimp contact mountable on the local terminal block and connect the cable.
Local terminal block: FUJIDENKI TV 603
Recommended crimp contact: NOHON CRIMP CONTACT CB100-S8 equivelent
( Type CB 100-8 conformable to the Japan Electrical Manufacturer’s Assciation Standard JEM1399).
-
When unloading and carrying, use the opening on the base plate of the compressor. The opening are large enough to fit forklift forks, which allows unloading and carying by a forklift.
- Be sure to read the section “Carrying in” of safety precaution on page 1-4 before starting work.
- Make sure the front cover is closed up to prevent it from opening unexpectedly.
1.2 Precautions for piping of Handsome II air compressor
- Vibration may be produced in a long, unsupported piping structure and be transmitted through the pipes, resulting in damage to the devices and components connected to the piping. Therefore, it’s necessary to fix such long piping with approciate supports ( lifting attachment, clamps, and/or uprights).
-
When two or more compressor are connected to the same main discharged air piping , be sure to install a stop valve, which can be closed when the compressor is stopped before the main discharged air piping.
- Incline the main discharged air piping toward the flow direction of the discharged air (downward) so that drain water does not stay in the main pipe.
- When there are recessed/ lowed or vertical section in the piping , be sure to provide a drain valve at the bottom of those section.
- Be sure to connect each discharged air piping to the top of the main discharged air piping to prevent drain water from flowing back.
1.3 Lubricating oil .
Precaution for lubrication- Use genuine brand lubricant, “KOBELCO GENUINE SCREW OIL” or the recommended oil listed below.
- Recommended lubricating oil.
Oil manufacturer | Brand |
Mobil Sekiyu K.K | Mobil Rarus 424 |
Showa Shell Sekiyu K.K | Shell Corena Oil S32 |
Showa Shell Shell Corena Oil S32 | |
ESO Sekiyu K.K | Newrex SHT32 |
- Never mix different brands of lubricating oil..
- Maintain the oil level between “H” and “L” during the operation..
- Do not operate with the oil level higher than “H”. Otherwise, oil may flow out into the discharged air and cause problems. (It is not abnormal that the oil level exceeds ‘H” when operation is stopped oil returns to the oil separator.
Refilling oil
- Press the stop button (red) to shut down the compressor and turn off the power switch. Nhấn nút màu đỏ để dừng máy nén và tắt công tắc điện.
- Turn off the earth leakage breaker.
- To open the oil supply port of the compressor and loosen the plug with a wrench.
- When closing the oil supply port , wipe off spilled oil completely and tighten the plug securely.
Unit: L
Type | HM37A/AD |
Amount | 18.0 |
Draining oil
- Press the STOP button (Red) to shut down the compressor and turn off the power switch.
- Turn off the earth leakage breaker.
- Open the drain valve located at the bottom of the oil separator, and the drain valve for the oil cooler to drain off the lubricating.
1.4.Power supply wiring
Selection of power supply transformer.If the transformer is too small or the wiring is too thin and too long, the motor may not accelerate sufficiently or may fail to start because of a sharp voltage drop at the start. Select a transformer of an adequate capacity for the motor considering proper wiring size and routing.
Selection of power supply breaker:
When installing the breaker for the main power supply, select an earth leakage circuit breaker.
- Recommended Earth leakage breakers.
Type | Voltage | Misubishi Electric | Toshiba | Fuji electric |
HM37A HM37AD | 200/200, 220 | MN225-SP 3P 150A | LMS225-3P 175 | SG203B/225 |
380, 400, 415/400, 440 | MN100-SP 3P 71A | LMS100-3P 90 | SG203B/150 |
Selection of cables
Power cable: 600V rated EV cables (600 V rated polyethylene cables)600V rated CV cables:
( JIS C306-93)
Remove the front cover of the enclosure and the power unit box cover, and connect the cables to the power supply terminals.
Earth wire:
- Connect the Earth wire to the Earth terminal (Marked with E) on the power supply terminal block.
- The Earth resistance should be 100Ω for 200, 220V and 10 Ω or less for 380, 400, 415, 440V, 415, 440V.
Type | Voltage | Cable(mm2) | Earth wire (mm2) | ||
Max.5m | Max.10m | Max.20m | Max.5m | ||
HM37A HM37AD | 200/200, 220 | 60 | 60 | 100 | 22 |
380, 400, 415/400, 440 | 22 | 22 | 38 |
Note: When using a cable with a sectional size more than 60mm2, use a relay terminal so that the cable size on the local side will be 60mm2, or select a crimp contact mountable on the local terminal block and connect the cable.
Local terminal block: FUJIDENKI TV 603
Recommended crimp contact: NOHON CRIMP CONTACT CB100-S8 equivelent
( Type CB 100-8 conformable to the Japan Electrical Manufacturer’s Assciation Standard JEM1399).
- The power to be supplied is 3-phase 200V (380, 400, 415 V) in the 50 Hz area and 3-phase 200V, 220V (400, 440V) in the 60 Hz area.
- The earth leakage breaker suitable for the machine should be mounted in the power unit..